2) Inspection of Storage Facilities for consumption at the Facility itself, in accordance with the provisions of Royal Decree 1523/1999.
- Periodic revisions every 5 years.
- Periodic inspection of the facilities with project every 10 years.
Periodic testing of tanks:
- Surface Tank Testing
- Tightness Testing of single-walled buried tanks without cover, optional:
- Every 5 years (if performed with product inside the tank).
- Every 10 years (if performed with empty tank, cleaned, degassed and thickness measured).
- Visual inspection and thickness measurement, if necessary due to poor condition.
Periodic testing of pipelines:
Testing of repaired tanks:
- First test at repair and every 10 years thereafter.
3) Inspection of Installations for supply to Vehicles, in accordance with the provisions of Royal Decree 706/2017.
- Periodic revisions every 5 years, for installations that do not require a project.
- Annual periodic reviews, for installations that require a project.
- Periodic inspection every 10 years, for installations requiring a project.
Periodic tests:
- Testing of Surface Tanks: Visual inspection and thickness measurement, if necessary due to poor condition.
- Tightness Testing of single-walled buried tanks without cover, optional:
- – Annually, it is carried out with product inside the tank.
- – Every 5 years, if performed with an empty, clean and degassed tank (including thickness measurement).
Pipe testing::
Testing of repaired tanks:
- 1st test at repair and every 10 years thereafter.
Corrosion protection:
- If the installation is equipped with an impressed current cathodic protection system, its proper functioning must be certified every two years.